EssEv‑0# Series Square‑Body aR Fast‑Acting ESS DC Fuse 1500VDC 50‑200A

EssEv‑0# square‑body aR fast‑acting DC fuse, 1500VDC 50‑200A,100kA breaking capacity for energy‑storage,battery‑pack and DC relay backup protection.

Selección de productos

Le ayudamos a encontrar los fusibles adecuados para su aplicación.

Apoyo técnico

Póngase en contacto con nuestro equipo para obtener detalles del producto y asistencia técnica.

Consultas sobre proyectos

Comente sus necesidades, cantidades y planes de compra.

¿Necesitas un fusible para tu proyecto?

Comparta con nosotros sus requisitos para obtener asesoramiento sobre productos y un presupuesto.

EssEv‑0# Series Square‑Body aR Fast‑Acting ESS DC Fuse 1500VDC 50‑200A

EssEv‑0# Series Square‑Body aR Fast‑Acting ESS DC Fuse 1500VDC 50‑200A is 0# size square‑body high‑speed aR‑class DC fuse for energy‑storage and new‑energy DC systems. Rated voltage 1500VDC, max interrupting capacity 100kA@1500VDC(L/R:10‑15ms), minimum breaking current>3In. Features ultra‑fast fault‑current interruption, excellent vibration & shock resistance ≥20g, compact square‑body construction. Referenced to UL‑248‑1/UL‑248‑13, IEC 60269‑1/IEC 60269‑4, RoHS compliant. Ideal for energy‑storage cabinet, battery‑pack and DC relay backup short‑circuit protection.

ESSEV-Series.-0.-50-200A-1500Vdc-IR-100kA-2

Características principales

  • Model Series: EssEv‑0# Square‑Body aR Fast‑Acting ESS DC Fuse
  • Rated Voltage: 1500 VDC
  • Current Range: 50A‑200A, Operation Class: aR (semiconductor short‑circuit protection)
  • Max Breaking Capacity:100kA @1500VDC (L/R:10‑15ms)
  • Minimum Breaking Current:>3 In
  • Ultra‑fast opening response under heavy DC fault‑current conditions
  • Compact 0# square‑body footprint for cabinet layout optimization
  • Excellent anti‑voltaic impingement, wide ambient temperature tolerance
  • High mechanical shock & vibration resistance ≥20g
  • Compliant: Referenced to UL‑248‑1/UL‑248‑13, IEC 60269‑1/IEC 60269‑4, RoHS; REACH available upon request

General Technical Specifications

Product SeriesEssEv‑0# Series Square‑Body aR Fast‑Acting ESS DC Fuse
Tensión nominal1500 V DC
Rango de corriente nominal50A‑200A (aR operation class)
Max Breaking Capacity100kA @1500VDC (L/R:10‑15ms)
Minimum Breaking Current>3 In
Body Size0# square‑body mounting type
Vibration Resistance≥20g
Standards ComplianceReferenced to UL‑248‑1/UL‑248‑13, IEC60269‑1/IEC60269‑4, RoHS
Temperatura de funcionamiento‑5℃ ~ +40℃(regular);‑40℃~+85℃(allowable)
Temperatura de almacenamiento‑40℃ ~ +120℃

Part Number List & Electrical Parameters(Test@1500VDC,100kA,L/R=12.5ms)

Número de piezaCorriente nominalMelting A²sClearing A²sPower Loss‑50%In(W)Power Loss‑100%In(W)
EssEv‑50A50A33017803.514.0
EssEv‑63A63A57030003.818.0
EssEv‑80A80A98553454.524.5
EssEv‑100A100A160086005.631.0
EssEv‑125A125A2880153606.840.0
EssEv‑150A150A5460289308.048.0
EssEv‑160A160A5850338009.558.0
EssEv‑175A175A66953650010.568.0
EssEv‑200A200A88004756012.077.0

Application Scenarios

EssEv‑0# Series Square‑Body aR Fast‑Acting ESS DC Fuse 1500VDC 50‑200A applies to new‑energy DC‑system projects: energy‑storage power station cabinets, energy‑storage battery‑pack protection, DC relay backup protection. The aR‑class high‑speed characteristic provides reliable short‑circuit protection for power semiconductors and DC components under heavy fault‑current conditions.

Installation & Operating Notes

  • Square‑body mounting design; ensure good bolt contact to avoid poor contact and over‑heating risk.
  • Recommended continuous operating current ≤75% of fuse rated‑current; apply temperature‑derating factor Kt when ambient temperature>40℃.
  • Altitude ≤2000m: no‑derating; for closed‑box installation within 2000‑4500m: derate 2%‑5% per 1000m elevation increase. Open‑air installation can normally ignore altitude influence; Insulation clearance needs re‑checking at high altitude, refer to GB/T16935.1.
  • Supports vertical, horizontal and inclined mounting; for spring‑contact‑type fuses, prevent adverse gravity‑vibration influence on electrical contact.
  • Forced air cooling can improve heat dissipation and increase allowable current, refer to Kv correction coefficient.
  • Do NOT replace fuse under live DC load unless equipped with certified load‑break switchgear.
  • Replace fuse immediately if mechanical damage, crack or deformation occurs on fuse body.
  • Additional reliability validation test shall be conducted for extremely high‑vibration working environments.
  • Select matched copper conductor cross‑section for terminals to control temperature‑rise performance.

Packing & Storage Requirements

Standard original‑box bulk package. Storage temperature:‑40℃~+120℃; humidity limit: RH≤70%@40℃, RH≤80%@30℃, RH≤90%@20℃. Sample testing support, OEM customization, stable mass‑volume supply for energy‑‑storage equipment manufacturers. REACH declaration available upon customer request.

Preguntas frecuentes

Q: What rating for EssEv‑0# Series Square‑Body aR Fast‑Acting ESS DC Fuse 1500VDC 50‑200A?
A: Rated 1500VDC, current range 50‑200A, aR‑class, max breaking capacity 100kA@1500VDC(L/R:10‑15ms), min breaking current>3In.

Q: What is aR‑class fuse?
A: aR‑class is semiconductor‑protecting high‑speed fuse class, designed for fast short‑circuit protection of power semiconductor devices.

Q: What is the body style of EssEv‑0# series?
A: Compact 0# square‑body mounting construction for energy‑‑storage cabinet installation.

Q: What standards does EssEv‑0# comply with?
A: Referenced to UL‑248‑1/UL‑248‑13, IEC60269‑1/IEC60269‑4, RoHS compliant; REACH document available on request.

Q: Main application scenarios for EssEv‑0# series?
A: Energy‑‑storage cabinet, battery‑pack and DC relay backup semiconductor short‑circuit protection.