High‑Speed Fuse GFEVT1500‑S‑105ES 400‑2000A 1500VDC Square Fuse
GFEVT1500‑S‑105ES square high‑speed 1500Vdc aR fuse,400‑2000A fast‑acting DC fuse,50kA interrupt rating,UL248‑13 & IEC60269‑4 certified for energy‑storage,wind‑power and battery‑pack short‑circuit protection.
Need a Fuse for Your Project?
Share your requirements with us for product guidance and a quotation.
GFEVT1500‑S‑105ES Square High‑Speed Fuse 400‑2000A 1500VDC DC Energy‑Storage Fuse
Our High‑Speed Fuse model GFEVT1500‑S‑105ES is square‑body fast‑acting aR‑class DC fuse for 1500Vdc new‑energy & energy‑storage systems, rated current from 400A‑2000A. It features 50kA high interrupting capacity, low arc‑voltage & low energy let‑through I²t, UL248‑13 & IEC60269‑4 compliant. Widely deployed for energy‑storage containers,battery packs,wind‑power equipment and DC‑drive short‑circuit & over‑current protection.
Main Electrical Ratings & Key Specifications
| Item | Parameter |
|---|---|
| Product Series Model | GFEVT1500‑S‑105ES |
| Rated Voltage | 1500 Vdc |
| Rated Current Range | 400A ~ 2000A , Size 4# |
| Interrupting Capacity | 50kA@1500Vdc (L/R ≤15ms) |
| Fuse Class | aR (partial‑range semiconductor protection) |
| Minimum Breaking Current | >3 In |
| Characteristic | Fast‑Acting High‑Speed DC Fuse, low I²t let‑through |
| Certifications & Standards | UL248‑13, IEC 60269‑4, RoHS Compliant; REACH statement upon request |
| Operating Temperature | ‑40℃ ~ +85℃; Standard working:‑5℃ ~ +40℃ |
| Mounting | 2pcs M12 bolts; Hole max depth 12.5mm, min thread‑length:12mm; Tin‑plated 3‑5μm |
| Typical Application | Energy‑storage ESS,battery‑pack,wind‑power,DC‑drive system short‑circuit protection |
Complete Model List | Melting / Clearing I²t & Power‑Loss Data
| Part Number | Rated Amps | Size | Melting A²s @50kA | Clearing A²s @50kA | Power Loss(W) |
|---|---|---|---|---|---|
| GFEVT1500‑400S‑105ES | 400A | 4# | 25,840 | 136,400 | 198 |
| GFEVT1500‑500S‑105ES | 500A | 4# | 57,350 | 275,430 | 200 |
| GFEVT1500‑630S‑105ES | 630A | 4# | 117,640 | 563,500 | 232 |
| GFEVT1500‑700S‑105ES | 700A | 4# | 164,320 | 783,000 | 249 |
| GFEVT1500‑800S‑105ES | 800A | 4# | 242,100 | 1,160,250 | 256 |
| GFEVT1500‑900S‑105ES | 900A | 4# | 345,700 | 1,668,800 | 277 |
| GFEVT1500‑1000S‑105ES | 1000A | 4# | 470,500 | 2,290,100 | 293 |
| GFEVT1500‑1100S‑105ES | 1100A | 4# | 625,200 | 3,005,000 | 312 |
| GFEVT1500‑1200S‑105ES | 1200A | 4# | 752,500 | 3,600,200 | 320 |
| GFEVT1500‑1250S‑105ES | 1250A | 4# | 915,200 | 4,430,000 | 325 |
| GFEVT1500‑1300S‑105ES | 1300A | 4# | 1,005,500 | 5,230,500 | 338 |
| GFEVT1500‑1350S‑105ES | 1350A | 4# | 1,290,000 | 6,245,000 | 348 |
| GFEVT1500‑1400S‑105ES | 1400A | 4# | 1,350,900 | 6,980,500 | 354 |
| GFEVT1500‑1500S‑105ES | 1500A | 4# | 1,580,560 | 7,630,000 | 362 |
| GFEVT1500‑1600S‑105ES | 1600A | 4# | 1,940,500 | 9,295,950 | 375 |
| GFEVT1500‑1800S‑105ES | 1800A | 4# | 2,728,600 | 13,120,650 | 394 |
| GFEVT1500‑2000S‑105ES | 2000A | 4# | 3,300,980 | 18,560,370 | 412 |
Mechanical Dimension
Square‑body construction, overall dimension 153±3 mm × 105±1.5 mm. 2‑pcs M12 mounting holes; max hole‑depth:12.5 mm, minimum thread‑length 12 mm. Terminals tin‑plated 3‑5 microns. Please check dimension drawing for full mechanical specifications.
Derating & Installation Instructions
- Recommended continuous operating current ≤ 75% of fuse rated‑current under standard‑5℃~40℃ ambient environment.
- For ambient temperature above 40℃, apply temperature‑derating factor Kt. For closed‑cabinet installation at altitude 2000‑4500 m, apply altitude‑derating Ka: derate 2‑5% per 1000‑meter elevation; open‑air deployment normally ignores altitude‑derating.
- Support vertical, horizontal and inclined mounting. Avoid gravity and vibration side‑effects for spring‑contact structures.
- Terminal contact resistance shall be kept low to prevent extra over‑heating and power‑loss rise.
Typical Applications
- Energy‑storage ESS container & DC main‑circuit protection
- Large‑capacity battery‑pack short‑circuit protection
- Wind‑power converter DC‑side protection
- DC drives and other 1500Vdc new‑energy power‑equipment over‑current & short‑circuit protection
Download Datasheet
GFHVT1500-S-105ES-Series.-400-2000A-1500Vdc-IR-50kA-4-Fast-Acting-fuse
Frequently Asked Questions
- What is rated voltage of GFEVT1500‑S‑105ES series?
- This high‑speed fuse is rated for 1500Vdc, designed for DC‑only new‑energy & energy‑storage circuits, not intended for AC‑system usage.
- What current ratings are available?
- 400A,500A,630A,700A,800A,900A,1000A,1100A,1200A,1250A,1300A,1350A,1400A,1500A,1600A,1800A,2000A (Size 4#).
- What is its interrupting capacity and fuse class?
- Interrupting capacity:50kA@1500Vdc(L/R ≤15ms); fuse class aR; minimum breaking current>3 In.
- What standards and certifications apply?
- Designed per UL248‑13 & IEC 60269‑4; RoHS‑compliant; REACH declaration can be supplied upon request.
- What is the rule for continuous‑current selection?
- Keep continuous working current ≤ 75% of fuse rated‑ampere under‑5℃~40℃ standard ambient.
- Must I derate for high‑temperature or high‑altitude?
- Yes. Above 40℃ apply temperature‑derating Kt. For closed‑box installation 2000‑4500 m altitude derate 2‑5% /1000 m; open‑air application generally skips altitude‑derating.
- Can I install this fuse horizontally or inclined?
- Vertical, horizontal and inclined mounting are allowed. Prevent gravity and vibration from degrading spring‑contact electrical connections.
- What are main target‑applications?
- ESS energy‑storage systems, battery‑pack, wind‑power converters,DC‑drives and other 1500Vdc new‑energy power‑equipment short‑circuit protection.
- Can I replace the fuse under live‑load?
- Do NOT replace fuse while carrying live‑load unless a matched fuse‑disconnector switch assembly is implemented.
- What are the storage conditions?
- Store in original package:‑40℃~+85℃, RH ≤70% at 40℃, dust‑free warehouse environment.