GFEVF150‑Series aR Semiconductor DC Power Fuse 125‑150VDC 70‑1000A
GFEVF150‑Series North‑American aR semiconductor DC power fuse, 125‑150VDC 70‑1000A, 50kA interrupting capacity for energy‑storage & DC‑drive protection.
GFEVF150‑Series aR Semiconductor DC Power Fuse 125‑150VDC 70‑1000A
GFEVF150‑Series aR Semiconductor DC Power Fuse 125‑150VDC 70‑1000A is north‑american standard high‑speed aR‑class semiconductor DC power fuse, rated for 125‑150VDC with max 50kA@150VDC breaking capacity, time constant 2.5±0.5 ms. Features low arc‑voltage, low I²t let‑through energy, low watt losses, superior cycling capability, excellent mechanical shock and vibration resistance. Supports parallel installation for higher ampacity within dimensional guidelines. Complies with UL‑248‑13, IEC 60269‑4, CE and RoHS. Widely used for energy‑storage battery‑pack, DC drives, power converters, rectifier equipment and DC relay backup semiconductor short‑circuit protection.
Key Features
- Model Series: GFEVF150 North‑American Style aR Semiconductor DC Power Fuse
- Rated Voltage: 125‑150 VDC
- Current Range: 70A‑1000A, Operation Class: aR (semiconductor short‑circuit protection)
- Max Breaking Capacity: 50kA @150VDC
- Time Constant: 2.5±0.5 ms
- Low arc‑voltage, low energy let‑through I²t characteristics
- Low watt losses, superior cycling capability
- Two body size options:70‑400A / 500‑1000A bolt‑on type
- Parallel mounting permitted for higher ampacity within dimensional guidelines
- Excellent mechanical shock & vibration resistance
- Compliant: UL‑248‑13, IEC 60269‑4, CE, RoHS; REACH available upon request
General Technical Specifications
| Product Series | GFEVF150‑Series North‑American Style aR Semiconductor DC Power Fuse |
| Rated Voltage | 125‑150 V DC |
| Rated Current Range | 70A‑1000A (aR operation class) |
| Max Breaking Capacity | 50kA @150VDC |
| Time Constant | 2.5±0.5 ms |
| Body Sizes | 70‑400A, 500‑1000A bolt‑on body versions |
| Standards Compliance | UL‑248‑13, IEC 60269‑4, CE, RoHS |
| Operating Temperature | ‑5℃ ~ +40℃(regular);‑40℃~+85℃(allowable) |
| Storage Temperature | ‑40℃ ~ +120℃ |
Part Number List & Electrical Parameters
| Part Number | Rated Current | Pre‑arc A²S | Clearing A²S @150V | Power Loss(W) |
| GFEVF150‑70A | 70A | 470 | 4000 | 6.9 |
| GFEVF150‑80A | 80A | 670 | 6000 | 7.7 |
| GFEVF150‑100A | 100A | 1200 | 12000 | 9.0 |
| GFEVF150‑125A | 125A | 1870 | 18000 | 11.2 |
| GFEVF150‑150A | 150A | 2700 | 26000 | 13.5 |
| GFEVF150‑200A | 200A | 4780 | 45000 | 17.6 |
| GFEVF150‑250A | 250A | 7470 | 70000 | 22.5 |
| GFEVF150‑300A | 300A | 10760 | 100000 | 27.0 |
| GFEVF150‑350A | 350A | 15700 | 140000 | 30.6 |
| GFEVF150‑400A | 400A | 20300 | 180000 | 35.2 |
| GFEVF150‑500A | 500A | 39000 | 120000 | 35.0 |
| GFEVF150‑600A | 600A | 46000 | 140000 | 47.0 |
| GFEVF150‑700A | 700A | 75000 | 220000 | 49.0 |
| GFEVF150‑800A | 800A | 92000 | 280000 | 58.0 |
| GFEVF150‑1000A | 1000A | 170000 | 510000 | 60.0 |
Application Scenarios
GFEVF150‑Series aR Semiconductor DC Power Fuse 125‑150VDC 70‑1000A is built for low‑voltage DC new‑energy applications: energy‑storage battery‑pack, DC drives, power converters, rectifier equipment and DC relay backup protection. The aR‑class high‑speed characteristic provides reliable short‑circuit protection for power semiconductor devices under heavy fault‑current conditions.
Installation & Operating Notes
- Bolt‑on mounting type; apply correct bolt torque value to avoid poor contact and over‑heating risk.
- Recommended continuous operating current ≤75% of fuse rated‑current; apply temperature‑derating factor for ambient temperature over 40℃.
- For closed‑box installation or altitude >2000 m: closed‑box environment requires 2%‑5% current derating per 1000 m altitude rise; open‑air installation can normally ignore altitude influence.
- Parallel mounting permitted only within dimensional and specification guidelines to achieve higher ampacity.
- Do NOT replace fuse under live DC load unless equipped with certified load‑break switchgear.
- Replace fuse immediately if mechanical damage, crack or deformation occurs on fuse body.
- Additional reliability validation test shall be conducted for extremely high‑vibration working environments.
- Select matched copper conductor cross‑section for terminals to control temperature‑rise performance.
Packing & Supply
Standard bulk package. Sample testing support, OEM customization, stable mass‑volume supply for energy‑storage and power‑converter manufacturers. REACH declaration available upon customer request.
자주 묻는 질문
Q: What rating for GFEVF150‑Series aR Semiconductor DC Power Fuse 125‑150VDC 70‑1000A?
A: Rated 125‑150VDC, current range 70‑1000A, aR semiconductor‑protection class, max breaking capacity up to 50kA@150VDC.
Q: What is aR‑class operation for this fuse?
A: aR class is semiconductor‑protecting high‑speed fuse class, designed for fast short‑circuit protection of power semiconductor devices.
Q: What body sizes are available?
A: Two bolt‑on body sizes:70‑400A and 500‑1000A for different current grades.
Q: What standards does GFEVF150‑Series comply with?
A: UL‑248‑13, IEC60269‑4, CE, RoHS compliant; REACH document available on request.
Q: Main application scenarios for GFEVF150‑Series?
A: Energy‑storage battery‑pack, DC drives, power converters, rectifiers and DC relay backup semiconductor short‑circuit protection.