High Speed DC Fuse‑GFEVT1000‑36 Series Square‑Body Fuse,25A‑250A 1000VDC,aR Class 50kA Breaking Capacity RoHS
GFEVT1000‑36 series high‑speed square‑body DC fuse,25A‑250A 1000VDC,aR‑class 50kA breaking capacity, RoHS REACH for EV and energy‑storage short‑circuit backup protection.
Dimensions (mm)

GFEVT1000‑36 Series High‑Speed Fuse is square‑body fast‑acting high speed dc fuse for partial‑range short‑circuit backup protection. aR performance class, rating 25A‑250A 1000VDC, max 50kA interrupting capacity with time constant ≤2±1 ms. Features low I²t, strong current‑limiting capability, low watt‑loss and superior cycling performance. RoHS compliant, REACH declaration available upon request. Widely deployed for electric vehicles, supercapacitor modules, rail transit, marine equipment and energy‑storage power‑system protection.
GFEVT1000-36-Series-25-250A-1000Vdc-fast-acting-fuse
Product At A Glance
| Item | Parameter |
|---|---|
| Product Series | GFEVT1000‑36 Series Square‑Body Fast‑Acting Fuse |
| Current Range | 25A‑250A |
| Rated Voltage | 1000VDC |
| Interrupting Capacity | 50kA @1000VDC; Minimum breaking current ≥3.0In |
| Time Constant | ≤2±1 ms |
| Performance Class | aR (Partial‑range semiconductor / power‑device backup protection) |
| Standards Reference | UL 248.1, UL248.13; IEC 60269‑1, IEC 60269‑4 |
| Compliance | RoHS compliant, REACH declaration available upon request |
| Mounting Torque | 11.0±1.0 N·m |
Model‑Specific Electrical Data @50kA 1000VDC
| Part Number | Rated Amps | Melting A²s | Clearing A²s | 100% Power Loss(W) | Installation Torque |
|---|---|---|---|---|---|
| GFEVT1000‑25A‑36 | 25A | 21 | 105 | 8 | 11.0±1.0 N·m |
| GFEVT1000‑32A‑36 | 32A | 38 | 185 | 10 | 11.0±1.0 N·m |
| GFEVT1000‑40A‑36 | 40A | 68 | 325 | 12 | 11.0±1.0 N·m |
| GFEVT1000‑50A‑36 | 50A | 155 | 745 | 16 | 11.0±1.0 N·m |
| GFEVT1000‑63A‑36 | 63A | 305 | 1450 | 20 | 11.0±1.0 N·m |
| GFEVT1000‑80A‑36 | 80A | 560 | 2480 | 22 | 11.0±1.0 N·m |
| GFEVT1000‑100A‑36 | 100A | 960 | 4820 | 25 | 11.0±1.0 N·m |
| GFEVT1000‑125A‑36 | 125A | 1640 | 8950 | 27 | 11.0±1.0 N·m |
| GFEVT1000‑160A‑36 | 160A | 4100 | 18750 | 36 | 11.0±1.0 N·m |
| GFEVT1000‑200A‑36 | 200A | 9560 | 39700 | 39 | 11.0±1.0 N·m |
| GFEVT1000‑225A‑36 | 225A | 11780 | 54700 | 42 | 11.0±1.0 N·m |
| GFEVT1000‑250A‑36 | 250A | 14500 | 70590 | 45 | 11.0±1.0 N·m |
Key Features & Benefits
- aR‑class partial‑range fast‑acting square‑body DC fuse, low I²t and powerful current‑limiting performance for semiconductor‑device backup short‑circuit protection
- High interrupting capacity:50kA @1000VDC; time constant ≤2±1 ms, minimum breaking current ≥3.0In
- Low watt‑loss, superior cycling capability, good temperature tolerance; vibration‑resistance ≥20g acceleration
- Supports derating correction for high‑temperature, high‑altitude and forced‑air‑cooling operating‑conditions
- Complies with UL 248.13, IEC 60269‑4; RoHS compliant, REACH documentation available upon export‑project request
Application Overview
GFEVT1000‑36 series square‑body high‑speed fuses serve as short‑circuit backup protection for new‑energy and industrial DC equipment. Widely used in EV / hybrid‑EV drive systems, supercapacitor modules, EV charging equipment, rail transit and marine power‑systems.
Critical Tip: Long‑term operating current shall be ≤75% of fuse rated‑current. Apply temperature‑altitude derating factors for enclosed cabinet working‑environments. Always cut‑off power before fuse replacement.
Installation & Operating Notes
- Mount fuse with specified installation torque:11.0±1.0 N·m to avoid abnormal over‑heating at terminals.
- Select copper conductor cross‑section according to datasheet requirement, guarantee stable contact performance.
- Long‑term continuous working current cannot exceed 75% of nominal fuse ampere rating.
- Implement current derating when ambient temperature>40℃ or installation altitude>2000 m in closed cabinets.
- Permitted for vertical, horizontal or inclined mounting; avoid gravity‑vibration interference for spring‑contact constructions.
- Replace immediately if fuse suffers mechanical damage; avoid live‑load fuse‑replacement unless equipment design permits.
Typical Applications
- Electric Vehicle & Hybrid‑EV drive‑system over‑current and short‑circuit backup protection
- Supercapacitor module power‑circuit protection
- EV charging equipment internal DC‑side protection
- Rail transit and marine vessel DC power‑system protection
- BESS energy‑storage equipment, converter‑inverter semiconductor‑device backup protection
Pair GFEVT1000‑36 series fuse with our matching heavy‑duty semiconductor fuse holders for complete high‑speed DC‑protection assembly.
Safety Reminders
- Disconnect full DC power before servicing or changing fuses. Strictly prohibit live‑line 1000VDC high‑voltage operation.
- Observe 75% rated‑current continuous‑working derating rule; extra derating required for high‑temp / high‑altitude enclosed‑cabinet installation.
- Select fuse breaking‑capacity higher than prospective short‑circuit‑current of your system.
- Refer to official datasheet for I‑t characteristic curve, derating curves and dimension drawings before mass‑procurement.
- Mechanically‑damaged fuse units must be discarded and replaced immediately.
자주 묻는 질문
Q: What is GFEVT1000‑36 series high‑speed fuse?
A: GFEVT1000‑36 is square‑body aR‑class fast‑acting DC fuse, rating 25A‑250A @1000VDC, 50kA interrupting capacity. For EV, supercapacitor, rail transit and energy‑storage backup short‑circuit protection, RoHS compliant, REACH available on request.
Q: What is the continuous‑current usage requirement?
A: Long‑term operating current must be ≤75% of fuse rated‑current. Additional derating is needed for high‑temperature and high‑altitude closed‑cabinet applications.
Q: What standards does this series comply with?
A: Reference standards UL248.1, UL248.13, IEC60269‑1, IEC60269‑4; RoHS compliant, REACH declaration can be supplied for overseas export‑projects.
Q: What is the installation torque requirement?
A: Installation torque:11.0±1.0 N·m. Improper torque will cause over‑heating under full‑load working‑condition.
Q: Where is GFEVT1000‑36 series mainly applied?
A: Mainly for EV / hybrid‑EV drive‑systems, supercapacitor modules, EV‑charging devices, rail transit, marine power‑systems and energy‑storage converter‑inverter semiconductor‑backup‑protection.
Request Quotation & Technical Support
Please provide target part‑number, order quantity, system short‑circuit‑current, temperature and altitude operating‑conditions. Our engineering team can deliver full datasheet, bulk‑price quotation and component‑selection guidance for EV, transportation and energy‑storage DC‑protection‑projects.
GFEVT1000‑36 Series High‑Speed Fuse · EssFuse. Confirm datasheet I²t, derating and dimension specs before mass‑production.